What is jumper in 25kv and 2x25kv OHE

What is jumper in 25kv and 2x25kv OHE

Jumper is a conductor which are used for connectivity between two conductors or equipments. The jumper should be flexible so that the required shape can be given to them easily to suit the requirement of the location.

Many types of jumpers are used in 25 kv & 2×25 kv OHE, Which are as follows-

  1. G- Jumper
  2. F – Jumper
  3. Anti theft jumper (ATJ)
  4. C-jumper
  5. F-jumper
  6. Feeder jumper
  7. Aluminium Large jumper
Jumper

To put a jumper in OHE, We need some PG (Parallel grooves). PG depends on the size of conductors(catenary, contact, LSW, ACW, Jumper ).

Now, We will read in details about the jumper used in OHE (2x25kv & 25kv) and the PG attached with them.

  1. Continuity jumper/G-Jumper

G-jumper is used in UIOL, turnout , diamond crossings and cross over for providing a parallel path for the current from one OHE shot to another OHE shot. This is a Flexible type copper stranded conductors.

Its length & diameter depends upon the diameter of the catenary and contact wires of OHE.

You can read about the size of G- jumper and the PG to be fitted with them in table no-1(2X25kv OHE) and table no-2(25kv OHE).

G-jumper
  1. F – Jumper

F jumper of approximately 50 mm square cross section is provided at insulated overlap to keep the current path between the cut in insulators and the nearest anchorage due to which spark is not generated in the cutting portion of the Catenary & Contact wires.

You can read about the size of F- jumper and the PG to be fitted with them in table no-1(2X25kv OHE) and table no-2(25kv OHE).

  1. Anti-theft jumper (ATJ)

Anti-theft jumper is used in out of run wire to prevent theft. It is made by cadmium copper material. The diameter of ATJ is 50 square mm.  it have 3 wires in a set (1.4 meters, 1.8 meters, 2.30 meters ).

Anti theft jumper
  1. C-jumper

C jumper is used to connect the Catenary wire and contact wire at every 350 m for providing a parallel path for the current between the them, so that the load current is proportionately shared by Catenary & contact wire.

You can read about the size of C- jumper and the PG to be fitted with them in table no-1(2X25kv OHE) and table no-2(25kv OHE).

C-jumper
  1. Feeder Jumper

Feeder jumper is used for connection between cross feeder to OHE.

It is also know as drop jumper in case of drop connection method jumpering.

Feeder jumper/Drop jumper
  1. Aluminium Large jumper

Aluminium large jumper is used at the locations where return conductors is required to be connected to track and to connect all aluminium bus terminal of SP, SSP, SS locations.

Aluminium large jumper

 

Table-1 [Jumper in 2x25kv, 50 Hz OHE , Where at- Catenary is 120 sqr.mm, Contact is 150 sqr.mm, ACW is 93.3 sqr.mm, LSW is 116.2 sqr.mm.
Sr. No.Type of jumper Properties of jumperReason to used PG requiredDistance from nearest support 
1G-jumper (150 sqr.mm )Flexible copper stranded conductors
Cross sectional area= 150 sqr.mm
Diameter  = 18.30 mm
Length = 4.20 mtrs
For providing feed path from one OHE shot to next OHE shotPG 120/160 in Catenary (4 nos)
PG 150/160 in Contact(4 nos)
5.60 mtrs from from nearest bracket
2F-jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 sqr.mm
Diameter  = 10.50 mm
Length = 1.60 mtrs
Used at IOL for feed continuities in cutting part of OR(out of run) wire.PG50/120 in Catenary (2 nos)
PG 50/150 in Contact (1 no)
2.5 mtrs from OR bracket
3ATJ- Jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 sqr.mm
Diameter  = 10.50 mm
Length = 1.30,1.80,2.40 mtrs
For prevent theftPG-50/120 In run catenary to out run catenary(6 nos)Adjusted from 15 to 20 mtrs
4H-Jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 sqr.mm
Diameter  = 10.50 mm
Length = 0.60 mtrs
For providing proper current in Anticreep wirePG-50/120 in Catenary to jumper
PG-50/93.3 in ACW to jumper (Bimetallic to be  used)
Not specified
5PH-Jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 sqr.mm
Diameter  = 10.50 mm
Length = 1.50 mtrs
For providing feed into LSW.PG-50/120 in Catenary to jumper
PG-50/116.3 in LSW to jumper (Bimetallic used)
Not specified
6T-jumper (150 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 150 sqr.mm
Diameter  = 18.30 mm
Length = 4.20 mtrs
for feed continuities in UIOLPG 120/160 in Catenary (4 nos)
PG 150/160 in Contact(4 nos)
5.60 mtrs from  nearest bracket
7Isolator jumper (Single pole)Flexible copper stranded conductors
Cross sectional area= 160 sqr.mm
Diameter  = 18.75 mm
Length = Depend upon implantation of mast & isolator arrangement
For feed sectioning in Catenary systemAs per requirement3.0 mtrs (Approx.)
8Isolator jumper (Double pole)Flexible copper stranded conductors
Cross sectional area= 160 sqr.mm
Diameter  = 18.75 mm
Length = Depend upon implantation of mast & isolator arrangement
For feed sectioning in Catenary & NFWAs per requirement3.0 mtrs (Approx.)

 

Table-2 [Jumper in 25kv, 50 Hz OHE, Where at- Catenary is 65 sqr.mm, Contact is 107 sqr.mm.
Sr. No.Type of jumper Properties of jumperReason to used PG requiredDistance from nearest support
1G-jumper (105 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 150 sqr.mm
Diameter  = 18.30 mm
Length = 3.80 mtrs to 4.10 mtrs
For providing feed path from one OHE shot to next OHE shotPG- 1031-2 = 8 nos5.60 mtrs from bracket
2G-jumper (160 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 150 mm sqr
Diameter  = 18.30 mm
Length = 3.80 mtrs to 4.10 mtrs
for feed continuities in OHEPG- 1031-3 = 8 nos5.60 mtrs from bracket
3F-jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 mm sqr
Diameter  = 10.50 mm
Length = 1.60 mtrs
Used in IOL for OR continuitiesPG- 1041-2 (2 nos)
PG 50/150 in Contact (1 no)
2.5 mtrs
4ATJ- Jumper (50 sqr.mm mm)Flexible copper stranded conductors
Cross sectional area= 50 mm sqr
Diameter  = 10.50 mm
Length = 1.40,1.80,2.10 mtrs(not specified)
For prevent theftPG 1041-2 In run catenary to out run catenary(6 nos) with 10×50 SS bolt(12 spring washer)Adjusted from 15 to 20 mtrs
5H-Jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 mm sqr
Diameter  = 10.50 mm
Length = 0.60 mtrs
For providing proper current in Anticreep wirePG-50/120 in Catenary to jumper
PG-50/93.3 in ACW to jumper (Bimetallic used)
Not specified
6PH-Jumper (50 sqr.mm)Flexible copper stranded conductors
Cross sectional area= 50 mm sqr
Diameter  = 10.50 mm
Length = 1.50 mtrs
For providing feed into LSW.PG-50/120 in Catenary to jumper
PG-50/116.3 in LSW to jumper (Bimetallic used)
Not specified
7T-jumper (150 mm sqr)Flaxible copper stranded conductors
Cross sectional area= 150 mm sqr
Diameter  = 18.30 mm
Length = 4.20 mtrs
For providing feed path from one OHE shot to next OHE shotPG- 1031-2 = 8 nos5.60 mtrs from bracket
8Isolator jumper (Single pole)Flexible copper stranded conductors
Cross sectional area= 160 mm sqr
Diameter  = 18.75 mm
Length = Depend upon implantation of mast & isolator arrangement
For feed sectioning in OHE systemAs per requirement3.0 mtrs (Approx.)
9Isolator jumper (Double pole)Flexible copper stranded conductors
Cross sectional area= 160 mm sqr
Diameter  = 18.75 mm
Length = Depend upon impanation of mast & isolator arrangement
For feed sectioning in OHE  systemAs per requirement3.0 mtrs (Approx.)
10C-jumperFlexible copper stranded conductors
Cross sectional area= 50 mm sqr
Diameter  = 10.50 mm
Length = 1.60 mtrs
for providing a parallel path for the current between catenary & contact wirePG-1041-2Every 350 mtrs